Customization: | Available |
---|---|
Certification: | RoHS, CB, CCC, ISO9001, CE |
Working Medium: | R32 |
Still deciding? Get samples of US$ 2500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Models | Air temp/outlet water temp | AH16DCR-R32 | COP | AH19SDCR-R32 | COP |
Heating capacity/Power input (KW) | at A20/W35°C | 21.88/3.66 | 5.98 | 25.4/4.5 | 5.64 |
at A7/W35°C | 16.3/3.34 | 4.88 | 18.7/4.06 | 4.61 | |
at A7/W45°C | 15.31/3.88 | 3.95 | 17.78/4.75 | 3.74 | |
at A2/W35°C | 14.49/3.23 | 4.49 | 16.8/3.97 | 4.23 | |
at A2/W45°C | 13.78/3.8 | 3.63 | 16/4.65 | 3.44 | |
Cooling Capacity/Power input(KW) | at A35/ W18ºC | 15.6/4.3 | 3.63 | 16.6/4.5 | 3.69 |
at A35/W7ºC | 11.4/4 | 2.85 | 12/4.2 | 2.86 | |
Compressor | Mitsubishi | Mitsubishi | |||
Max.currentt (A) | 25 | 9 | |||
Electric supply | 230V/50-60Hz | 400V/50~60HZ | |||
Max.water temperature ( oC) | 60 | ||||
Running temperature range (oC) | '-25 ~ 43 | ||||
Refrigerant circuit | Refrigerant | R32 | |||
DC Inverter compressor(s) | Twin Rotary | ||||
Heat exchange | Copper and Hydrauphilic Aluminum Fin | ||||
Air flow (m3/h) | 5600 | 5600 | |||
Water circuit | Heat exchanger | ||||
In/Out pipe | DN32 | ||||
Water flow (m3/h) | ≥2.3 | ≥2.3 | |||
permitted pressure | ≤0.8MPa | ||||
Unit dimensions WxHxD (mm) | 1115*1280*425 | 1115*1280*425 | |||
Pacage dimensions WxHxD (mm) | 1170*1550*500 | 1170*1550*500 | |||
Net weight (Kg) | 140 | 140 | |||
Gross weight (Kg) | 150 | 150 | |||
Noise level (dB(A)) | 52 | 52 | |||
Loading quantity for 20'/40' | 22/44 | 22/44 |